Oil Detector Tubes

Download Brochure

Oil Detector Tubes

Part Number: RT752C

Using the Checkmate device, a drop of oil can be milked off the suction side of a system. The Oil will be seen wetting through the Detector Tubes’ Transfer Agent. As the Oil passes through the Transfer Agent a dye fraction will release and stain the Indicator Segment. The color captured by in the Indicator is compared against a color chart.

Simply insert a Detector Tube into the Checkmate body and connect inline to a cylinder or on the low side of the system. Detector Tube results take less than one minute.

The Checkmate method is the industry’s only valid field test for measuring acid and moisture levels in both the compressor oil and any refrigerant gas. The Detector Tubes have been tested for accuracy by Intertek Testing Services, an ARI approved laboratory.

  • Heavy wall pyrex glass is used on each tube and packed under dry nitrogen, and the high quality brass body is coupled with HG 316 stainless steel needles.

  • Refrigerant oils are the opposite of engine oil in nature. They are hygroscopic (absorb moisture), and engine or petroleum oils are hydroscopic (repel moisture).

  • ISO4406 states that PAG and POE oils must not exceed a moisture content of 350ppm.